Spectrosys Alarm / control unit Flopurge TS


Product Features
- Automatic purge controller
- Alarm and control unit for max. 10 digital inputs (e.g. contact pressure gauge or pressure switch), 8 analogue inputs (e.g. pressure transmitters) and one additional input for emergency shut off
- The unit may be used for 1 purge system including 3 pneumatic valves and 1 more individually programmable pneumatic valve
- User adjustable vent timer, pressurisation timer and purge cycles
- User selectable ACV (pn. operated cylinder valve) option or Extra Downstream EMO option
- Touchscreen Operation: All operation from ergonomically positioned Human Machine Interface
- Industrial PLC controls all inputs and outputs as well as analogue signal processing
- 4 potential free outputs (one for each valve status)
- Communication options: Ethernet, Profibus, Modbus RT and DeviceNet communications
- Solenoid valves can be manually operated by user
- Daylight visible LED indicators
- Acoustic signals can be silenced
- Digital inputs to be configured for NO or NC contacts
- Plastic housing IP 65 for wall mounting
- Password protection for 2 superior levels of access
- Multiple Language Support: supports up to four languages as standard
- According to EC Directive 2004/108/EC (immunity and emission standard, measurement, control and laboratory use)
- According to Low Voltage Directive 2006/95/EC
Technical Data
Housing
Protection class: IP 65
Dimensions (WxHxD): 300 x 200 x 180 mm
Dimensions (WxHxD): 300 x 200 x 180 mm
Compatibility inputs
- mechanical switches
- 4-20 mA transducers
- 4-20 mA transducers
Digital inputs
Power supply voltage: 24 V DC
Max. power: 15 mA (per channel)
Max. power: 15 mA (per channel)
Analogue inputs
Max. voltage (open circuit): 24 V DC
Short circuit current: 25 mA
Short circuit current: 25 mA
Output / pneumatic valves
Max. pressure: 7 bar
Compatibility: inert gases
Compatibility: inert gases
Power supply voltage
100-240V / 50-60Hz
Max. power consumption: 2 A
Max. power consumption: 2 A
Internal signals
- LEDs 17 mm
- buzzer
- buzzer
NAMUR-Specification
Voltage: 5 V DC - 25 V DC
Power input inactive: IL < 1 mA
Power input activated: 3 mA < IL < 15 mA
Power input inactive: IL < 1 mA
Power input activated: 3 mA < IL < 15 mA
Downloads
spectrosys