Spectrosys Alarm / control unit Flocontrol TS

Product Features

  • Automatic Controller capable of supporting:
    - Single Gas Panels
    - Single Gas Panels with supporting purge
    - Twin Gas panels (different source and destination)
    - Dual gas panels (same source and destination with auto changeover facility)
    - Supports MP3 and SBE3 configurations
  • Alarm and control unit for 5 external digital sensor inputs, 8 system analogue inputs and 6 system digital inputs
  • User adjustable purge cycles and  service mode set points
  • Line capacity calculator for optimised line purging
  • Exhaust failure switch fitted as standard
  • User selectable ACV (pn. operated cylinder valve)
  • Touchscreen Operation: All operation from ergonomically positioned Human Machine Interface
  • Industrial PLC controls all inputs and outputs as well as analogue signal processing
  • 2 potential free outputs (one each for warning or shutdown conditions)
  • Communication options: Ethernet, Profibus, Modbus RT and DeviceNet communications
  • Solenoid valves can be manually operated by user
    • An external junction box is supplied in order to allow fast connection of external sensors (e.g. gas detection) to the Flocontrol TS via a supplied 3 metre pre-plugged lead.
  • Optional Heating Control System Add-on box for cylinder jackets and panel heating
  • Digital inputs to be configured for NO or NC contacts
  • Plastic housing IP 65 for wall mounting
  • According to EC Directive 2004/108/EC (immunity and emission standard, measurement, control and laboratory use)
  • According to Low Voltage Directive 2006/95/EC
  • ATEX Equipment Directive 94/9/EC (Category 3 compliant where stated on the rating plate)

Alarm and control systems for gas supply equipment

    Technical Data
    Housing
    Protection class: IP 65
    Dimensions (WxHxD): 635 x 220 x 200 mm
    depending on cabinet: 800 x 220 x 200 mm
    Compatibility inputs
    - mechanical switches
    - 4-20 mA transducers
    Digital inputs
    Power supply voltage: 24 V DC
    Max. power: 15 mA (per channel)
    Analogue inputs
    Max. voltage (open circuit): 24 V DC
    Short circuit current: 25 mA
    Output / pneumatic valves
    Max. pressure: 7 bar
    Compatibility: inert gases
    Power supply voltage
    100-240V / 50-60Hz
    Max. power consumption: 2 A
    Internal signals
    - LEDs 17 mm
    - buzzer
    NAMUR-Specification
    Voltage: 5 V DC - 25 V DC
    Power input inactive: IL < 1 mA
    Power input activated: 3 mA < IL < 15 mA
    spectrosys
    FloControl
    Spectrosys Alarm / control unit Flocontrol TS

    Questions about the product? Let us know.

    Contact our experts